Shopping security
The Honeywell FC-RO-1024 is a 24-channel Remote Output (RO) module designed for Safety Manager systems, including SM and FSC platforms. It provides reliable digital output control for actuators such as solenoid valves, motor starters, and indicator lights in safety-instrumented systems (SIS). Built for SIL 3 applications, this module ensures that outputs default to a safe state under fault conditions, making it suitable for emergency shutdown (ESD), fire and gas (F&G), and burner management systems (BMS).
| Feature | Specification |
|---|---|
| Module Type | Remote Output (RO) |
| Series | Honeywell Safety Manager / FSC |
| Number of Channels | 24 independent digital outputs |
| Output Voltage | 24 Vdc nominal |
| Output Current | 1.0 A per channel |
| Safety Integrity Level | SIL 3 compliant |
| Loop Monitoring | Detects open and short circuits in field wiring |
| Failsafe Logic | Outputs de-energize during fault or loss of communication |
| Internal Diagnostics | Continuous self-testing of switching components |
| Electrical Isolation | Galvanic isolation between field and system bus |
| Short-Circuit Protection | Integrated per channel |
| Redundancy | Supports dual-modular configuration for high availability |
| Status Indicators | Individual LED for each channel (On/Off/Fault) |
| Power Consumption | Approx. 2.5 W for internal electronics |
| Physical Dimensions | 4TE width × 3 HE height |
| Weight | 0.3 kg |
Emergency Shutdown (ESD): Controls critical valves and devices to isolate hazards safely.
Fire & Gas (F&G) Systems: Operates suppression valves, alarms, and fire safety equipment.
Burner Management (BMS): Ensures safe sequencing and shutdown of fuel valves in boilers and furnaces.
Ensure the total current of all channels does not exceed the power supply capacity of the I/O rack. Full-load operation on all 24 channels requires careful thermal management. Proper wiring and grounding are essential to maintain diagnostic accuracy and SIL 3 compliance.
Q: Can FC-RO-1024 handle inductive loads?
A: Yes, but external suppression diodes are recommended to protect the module from voltage spikes.
Q: Is this module compatible with older Safety Manager systems?
A: It is compatible with SM and FSC series controllers; always verify firmware versions for full functionality.
Q: What happens if communication with the controller is lost?
A: The module will automatically de-energize all outputs to maintain a safe state.
Q: Can multiple FC-RO-1024 modules be used redundantly?
A: Yes, dual-modular redundancy configurations are supported to enhance system availability.
Ships within 48 hours · Estimated delivery Jul 2 - Jul 7
US$40
Get nowSign up to your membership to get coupons up to
15%
Get nowOpportunity to enjoy order discount up to 15% off
Top-Converting Item to Boost Your Average Order