Shopping security
Configured for executing final switching commands via SafeEthernet in safety-related controllers, the HIMA F2DO801 (F2DO801 Safety Digital Output Module) provides direct physical/electrical execution.
| Parameter | Specification |
|---|---|
| Model | F2DO801 |
| Brand | HIMA |
| Origin | Germany |
| Module Type | Safety Digital Output Module |
| Safety Certification | IEC 61508 SIL 3, IEC 61511 SIL 3 |
| Output Channels | 8 independent fail-safe relay outputs |
| Output Type | Relay-based, electrically isolated |
| Operating Voltage | 24 VDC, -15% to +20% |
| Current Input | 0.6 A maximum |
| Output Current per Channel | 0.5 A (short-circuit proof) |
| Response Time | 20 ms or greater |
| Ethernet Interfaces | 2 x RJ-45, 10BASE-T/100BASE-Tx with integrated switch |
| External Fuse | 10 A time-lag (T) |
| Protection Class | IP20 |
| Power Consumption | 14.4 W maximum |
| Operating Temp | 0 to 60 deg C |
| Storage Temp | -40 to 85 deg C |
| Dimensions | 207 x 114 x 86 mm |
| Weight | 1.3 kg |
The F2DO801 is cross-examined and validated under strict structural guidelines to sustain compliance with SIL3 certification metrics. Operating via a "de-energize to trip" processing mechanism, the unit commands all 8 internal relays to drop out and assume a de-energized safe state if a critical system fault occurs. Integrated galvanic isolation separates the logic components from the field terminal blocks, preventing external faults from destabilizing the internal safety controller. If a localized, channel-specific failure is found through real-time load fault diagnostics, the internal logic executes a single-channel fail-safe state execution, maintaining complete availability across the remaining non-faulted circuits.
Q: How does the F2DO801 manage localized channel faults versus complete module faults?
A: Internal diagnostic loops continuously monitor for short circuits, open circuits, and load faults. A channel-specific problem causes only the affected channel relay to drop out, while a system-wide hardware failure causes the module to drop power to all 8 safety relay outputs.
Q: Can the internal switch on the Ethernet interfaces be configured to handle safe communication traffic?
A: Yes. The 2 x RJ-45 interfaces operate on 10/100BASE-Tx networks and use SafeEthernet data encapsulation to verify packet integrity and latency requirements before driving any output load commands.
Q: What are the external circuit protection specifications for the module power distribution?
A: The module power lines must be protected upstream by an external 10 A time-lag (T) fuse, and input power must originate from a power supply unit providing safe insulation per IEC 61131-2.
Ships within 48 hours · Estimated delivery Jul 5 - Jul 10